Add to Cart
JVR1000 Three Phase Voltage Monitoring Relay3 Phase Sequence Relay 380VAC 50Hz
♦ Protective Functions
-- Phase sequence
-- Phase loss
-- Phase unbalance
-- Overvoltage
-- Undervoltage
Applications Pumps / Fans Blowers / Motors / Compressors ,have the CE CCC Certain ,make sure every product Quality ,Meet industry standards
♦ Technical data
Type | JVR1000 |
Measuring circuit | L1,L2,L3 |
Rated voltage | 380VAC ,50Hz |
Monitoring functions | phase sequence, phase loss, overvolatege, undervoltage,phase unbalance |
Overvoltage setting range | 390-490V adjustable |
Undervoltage setting range | 300-470V adjustable |
Hysteresis | 10V |
Delay time for overvoltage and undervoltage | 0.1-25s adjustable |
Phase unbalance setting range | 5%-29% adjustable |
Delay time for phase unbalance | 1-25s adjustable |
Delay time for phase loss | 1s |
Delay time for phase sequence | instant |
Indicators | LCD indicating voltage,current,operation status |
Output contacts | 1 NO,1NC |
Contact capacity | 6A ,250VAC |
Dimensions (H x W x D) | 80×40×54mm |
Mounting | DIN rail |
In many three-phase AC applications, the correct phase sequence is sometimes a necessary condition. Incorrect phase sequence or phase loss may cause the device to work abnormally or even be damaged.
The phase sequence relay can be regarded as a three-phase asynchronous motor with long-term operation in the locked state in terms of function and structure. Its structure diagram and one-phase equivalent circuit are shown in the figure.
Phase sequence relay can be widely used in three-phase electric applications, with indicator light as phase sequence indicator, combined with contactor to complete automatic commutation function