Wenzhou Ginri Power Automation Co., Ltd.

Wenzhou Ginri Power Automation Co., Ltd.

Manufacturer from China
Active Member
8 Years
Home / Products / Three Phase Voltage Monitoring Relay /

JVR1000 Three Phase Voltage Monitoring Relay3 Phase Sequence Relay 380VAC 50Hz

Contact Now
Wenzhou Ginri Power Automation Co., Ltd.
Province/State:zhejiang
Country/Region:china
Contact Now

JVR1000 Three Phase Voltage Monitoring Relay3 Phase Sequence Relay 380VAC 50Hz

Ask Latest Price
Brand Name :GINRI
Model Number :JVR1000
Place of Origin :CHINA
MOQ :50Pcs
Payment Terms :L/C, T/T, Western Union,Paypal
Supply Ability :20000Pcs
Delivery Time :7 -10 working days
Packaging Details :1 relay in 1 box
Certification :CE
Voltage Range :300-490V
measuring circuit :L1,L2,L3
Reset :Manual or Power Cycle
Contact :SPDT
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

JVR1000 Three Phase Voltage Monitoring Relay3 Phase Sequence Relay 380VAC 50Hz

♦ Protective Functions

-- Phase sequence

-- Phase loss

-- Phase unbalance

-- Overvoltage

-- Undervoltage

Applications Pumps / Fans Blowers / Motors / Compressors ,have the CE CCC Certain ,make sure every product Quality ,Meet industry standards

♦ Technical data

Type JVR1000
Measuring circuit L1,L2,L3
Rated voltage 380VAC ,50Hz
Monitoring functions phase sequence, phase loss, overvolatege, undervoltage,phase unbalance
Overvoltage setting range 390-490V adjustable
Undervoltage setting range 300-470V adjustable
Hysteresis 10V
Delay time for overvoltage and undervoltage 0.1-25s adjustable
Phase unbalance setting range 5%-29% adjustable
Delay time for phase unbalance 1-25s adjustable
Delay time for phase loss 1s
Delay time for phase sequence instant
Indicators LCD indicating voltage,current,operation status
Output contacts 1 NO,1NC
Contact capacity 6A ,250VAC
Dimensions (H x W x D) 80×40×54mm
Mounting DIN rail

JVR1000 Three Phase Voltage Monitoring Relay3 Phase Sequence Relay 380VAC 50Hz

In many three-phase AC applications, the correct phase sequence is sometimes a necessary condition. Incorrect phase sequence or phase loss may cause the device to work abnormally or even be damaged.

The phase sequence relay can be regarded as a three-phase asynchronous motor with long-term operation in the locked state in terms of function and structure. Its structure diagram and one-phase equivalent circuit are shown in the figure.

Phase sequence relay can be widely used in three-phase electric applications, with indicator light as phase sequence indicator, combined with contactor to complete automatic commutation function